Wheelock MT-24-LS Manuel d'installation

Naviguer en ligne ou télécharger Manuel d'installation pour Détecteurs de fumée Wheelock MT-24-LS. Wheelock MT-24-LS Installation manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 34
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
150933 / Rev. 9/96 1
1. Introduction
The Model 5395 is a notification and auxiliary power expander that provides up to 6 amps of
regulated, 24 volt power for powering notification appliances and auxiliary devices. The 5395
provides its own AC power connection, battery charging circuit, and battery connections. Used
with security and fire panels, the 5395 enables you to connect and distribute power to many more
devices than your panel may normally allow.
Comparison to the Silent Knight Model 5295
The 5395 signal inputs operate the same way as the signal inputs on the Model 5295 Signal
Power Expander. Two of the configurations described on page 5 are the same as the two
configurations on the 5295. However, pay close attention to the output and input terminal
numbers before replacing a Model 5295 with the Model 5395. The terminal assignments of
inputs 1 and 2 are reversed on the 5395, and there are additional terminals on the 5395 that
are not on the 5295 panel.
Input Configurations
The 5395 has two optically isolated signaling inputs that provide the signal connection from
the main control panel to the 5395 (see page 4 for more details).
Output Configurations
The 5395 has four power-limited notification outputs that can be configured in various
combinations of class A and Class B circuits (see page 5 for more details).
Auxiliary Power Configurations
The 5395 has a dedicated, power-limited, auxiliary output that can be configured in two
different ways. The auxiliary output can either be non-resettable (always on), or configured
to switch off when the AC power goes off to conserve the battery standby power. When the
auxiliary power is configured to switch off, there is a 30 second delay before the auxiliary
power is turned off after the AC power goes off (see page 19 for more details).
Form C Trouble Relay
The 5395 includes a general trouble relay that will de-energize for any trouble situation on
the 5395 (see page 12 for more details).
Earth Fault Detection
The 5395 monitors for earth faults to the system power or system ground. When detected,
the system de-energizes the trouble relay and the input supervision relays (see page 28 for
details).
ANSI Temporal Code
The 5395 provides two configuration options that will drive outputs with the ANSI temporal
code if the inputs are on constant (see page 18 for details).
Vue de la page 0
1 2 3 4 5 6 ... 33 34

Résumé du contenu

Page 1 - 1. Introduction

150933 / Rev. 9/96 11. IntroductionThe Model 5395 is a notification and auxiliary power expander that provides up to 6 amps ofregulated, 24 volt power

Page 2 - 2. UL Requirements

Model 5395 Distributed Power Module10 150933 / Rev. 9/96(This page left blank in case of removal.)

Page 3 - 3. System Overview

Installation Manual150933 / Rev. 9/96 114.4 Connecting the 5395 to a Control PanelFigure 4-2 shows the general layout of the 5395 PC board. This sect

Page 4 - 3.2 Signal Input Terminals

Model 5395 Distributed Power Module12 150933 / Rev. 9/96Consult your control panel manual for specific wiring information on the control panel beingus

Page 5

Installation Manual150933 / Rev. 9/96 13Class A Supervised Input CircuitsThe configuration shown in Figure 4-4 shows class A supervised wiring from a

Page 6 - 4. Installation

Model 5395 Distributed Power Module14 150933 / Rev. 9/96Class B Supervised Input CircuitsFigure 4-5 shows class B supervised wiring from a fire panel

Page 7 - 4.2 Wire Routing

Installation Manual150933 / Rev. 9/96 154.5 UL Listed Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.

Page 8

Model 5395 Distributed Power Module16 150933 / Rev. 9/96continued from previous pageManufacturer Model Number Device TypeWheelock ET-1080-WM-24-VF-W S

Page 9

Installation Manual150933 / Rev. 9/96 174.7 DIP Switch SettingsA 5-position DIP switch on the 5395 board allows you to select the following:• How long

Page 10 - 10 150933 / Rev. 9/96

Model 5395 Distributed Power Module18 150933 / Rev. 9/96*Switch1,3ONSwitch2OFF* See the following information about ANSI temporal-coded outputsSwitch1

Page 11 - PC Board

Installation Manual150933 / Rev. 9/96 194.7.2 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 6 hours.The ON position is for

Page 12 - 4.4.1 Trouble Relay

Model 5395 Distributed Power Module2 150933 / Rev. 9/962. UL RequirementsWhen installed in accordance with NFPA 72 rules, the 5395 is listed to meet U

Page 13 - Installation Manual

Model 5395 Distributed Power Module20 150933 / Rev. 9/965. Connection to Silent Knight PanelsThe drawings in this section show you how to connect the

Page 14 - 14 150933 / Rev. 9/96

Installation Manual150933 / Rev. 9/96 211211109876543Model5204 or5204PL9Model 76284.7k EOL101112 1314 151617 18 19Model5395Input 2 Input 1TroubleRelay

Page 15

Model 5395 Distributed Power Module22 150933 / Rev. 9/9623* Term. 34 (Zone 12) used as an example.34*38119181778 11--++667221539541604720Supervision3

Page 16 - 4.6 Battery Connection

Installation Manual150933 / Rev. 9/96 236. Sample ApplicationsThe drawings in this section show various 5395 configurations, including daisy-chaining.

Page 17 - 4.7 DIP Switch Settings

Model 5395 Distributed Power Module24 150933 / Rev. 9/96120 VAC120 VACNotification CircuitNotification CircuitModel 5395Model 5395Local Fire ControlOu

Page 18 - Temporal-coded Options

Installation Manual150933 / Rev. 9/96 25Input 1Input 2Input 1Input 1Notification Circuit 1Notification Circuit 2Outputs Active whenOutputs Active when

Page 19

Model 5395 Distributed Power Module26 150933 / Rev. 9/966.2 Non-Resettable Power ApplicationThe 5395 provides a dedicated 3-amp auxiliary power output

Page 20 - 20 150933 / Rev. 9/96

Installation Manual150933 / Rev. 9/96 277. TroubleshootingLight-emitting diodes (LEDs) indicate fault conditions. This section describes the LED stat

Page 21

Model 5395 Distributed Power Module28 150933 / Rev. 9/967.2 Trouble ConditionsTrouble Condition What HappensLow AC(AC input voltage is low oroff for 6

Page 22 - Supervision

150933 / Rev. 9/97 A-1AppendixUL Listed Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL res

Page 23 - 6. Sample Applications

Installation Manual150933 / Rev. 9/96 33. System OverviewCAUTIONEach output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will

Page 24 - Local Fire Control

Model 5395 Distributed Power ModuleA-2 150933 / Rev. 9/97Faraday 5522 4” Square Sync StrobeFaraday 6120 HornFaraday 6140 HornFaraday 6223 Horn Faraday

Page 25 - 150933 / Rev. 9/96 25

Appendix150933 / Rev. 9/97 A-3System Sensor SS2475ADA StrobeSystem Sensor PS2415ADA Mini-Horn/StrobeSystem Sensor PS241575ADA Mini-Horn/StrobeSystem S

Page 26 - 6.3 Door Holder Application

Model 5395 Distributed Power ModuleA-4 150933 / Rev. 9/97Wheelock CH-CF1-LS-24-CFW Strobe ChimeWheelock CH-CF1-MS-24-CFW Strobe ChimeWheelock CH-CF1

Page 27 - 7. Troubleshooting

Appendix150933 / Rev. 9/97 A-5Wheelock MBS-G6-24-W-HF-R Motor Bell with StrobeWheelock MBS-G10-24-W-HF-R Motor Bell with StrobeWheelock MIZ-24-R Min

Page 28 - 7.2 Trouble Conditions

Model 5395 Distributed Power ModuleA-6 150933 / Rev. 9/97Wheelock SR-2415-VFR Sync StrobeWheelock SRP-2415-HFR Sync StrobeWheelock SR-241575-VFR Sy

Page 29 - Appendix

Model 5395 Distributed Power Module4 150933 / Rev. 9/963.2 Signal Input TerminalsTerminals 14 through 19 are polarized signal input terminals. They p

Page 30 - A-2 150933 / Rev. 9/97

Installation Manual150933 / Rev. 9/96 53.3 Notification Output TerminalsTerminals 3 through 10 are the notification output terminals. Each of the fo

Page 31 - 150933 / Rev. 9/97 A-3

Model 5395 Distributed Power Module6 150933 / Rev. 9/964. InstallationBefore installing the 5395, the AC input must first be wired into the building’s

Page 32 - A-4 150933 / Rev. 9/97

Installation Manual150933 / Rev. 9/96 74.2 Wire RoutingTo avoid induced noise (transfer of electrical energy from one wire to another), keep input wir

Page 33 - 150933 / Rev. 9/97 A-5

Model 5395 Distributed Power Module8 150933 / Rev. 9/964.3 Current Requirements (Standby and Alarm)4.3.1 Current Drawn From Host PanelTable 4-1 shows

Page 34 - A-6 150933 / Rev. 9/97

Installation Manual150933 / Rev. 9/96 9Table 4-2. Battery Calculation WorksheetDevice NumberofDevicesCurrent per Device StandbyCurrentAlarmCurrentFor

Commentaires sur ces manuels

Pas de commentaire